Overview
The PC4664 is a MAXSYS graphic annunciator kit that displays zone status, troubles, device operation, and system events at a glance on a wall-mounted graphic layout. The PC4664 shows up to 64 events on a 11" × 17" (279 × 432 mm) display. It connects to PC4010/PC4020 MAXSYS panels over Combus and is programmed from an enrolled LCD keypad or DLS downloading software—same workflow as the rest of the MAXSYS system.
The companion PC4632 model offers 32 events on a smaller display; setup and programming are similar (see shared install manual).
At a Glance
| Specification | PC4664 |
|---|---|
| Display capacity | Up to 64 events |
| Display size | 11" × 17" (279 × 432 mm) |
| Host panel | PC4010 / PC4020 MAXSYS |
| Bus connection | Combus (4-wire) |
| Programming | LCD4500/LCD4501 keypad or DLS download |
| Output driver | Enrolled as PC4216 low-power output module |
| Indicators | Zone open/close, troubles, device operation, system status |
| Typical use | manufacturing plants, warehouses, large offices, and residential apartment buildings |
Before You Install One
Complete these PC4020 steps first:
- Plan and wire the PC4020 system (install manual).
- Install panel, power, and at least one LCD keypad for programming.
- Install and enroll zone expander modules (PC4108A, PC4116).
- Install and enroll detectors in final locations—makes annunciator layout planning accurate.
Then plan annunciator layout artwork (supplied templates or custom), Combus homerun, tamper, and LED matrix wiring.
Official Sources
- Product page: DSC MAXSYS 64 Point Graphic Annunciators (ID 34)
- PC4632/PC4664 Installation Manual v1.0 (English NA) — DSC official documentation
- MAXSYS engineer specification sheet — system context
Error Codes
The PC4664 does not maintain a separate end-user trouble code table—it reflects PC4020 system troubles and Combus module faults on its graphic display and follows host panel trouble logic.
What the Annunciator Shows
| Indication | Meaning |
|---|---|
| Zone open/close icons | Real-time zone state per programmed layout |
| Trouble indicators | Host panel troubles (battery, AC, FTC, zone fault, etc.) |
| Device operation | Programmed PGM/output or access events |
| Blank / frozen display | Combus comms loss, power loss, or PC4216 enrollment fault |
Host Panel Troubles Affecting Display
When the graphic display stops updating, check **[*, 2]** on the host PC4020 keypad for:
| Host trouble | Effect on annunciator |
|---|---|
| Aux Supply Troub | PC4216 output overload—display may dim or fail |
| Module E fault on PC4216 slot | Communications lost—display frozen |
| Module LV fault | Insufficient Combus power—intermittent updates |
| Module T tamper | Annunciator enclosure tamper |
Run host diagnostics [04] to identify the PC4216 module number assigned to the annunciator.
Source: PC4632/PC4664 Installation Manual; PC4020 v3.5 Installation Manual §16.
| Code / display | Meaning | What to do |
|---|---|---|
| Indication | Meaning | |
| Zone open/close icons | Real-time zone state per programmed layout | |
| Trouble indicators | Host panel troubles (battery, AC, FTC, zone fault, etc.) | |
| Device operation | Programmed PGM/output or access events | |
| Blank / frozen display | Combus comms loss, power loss, or PC4216 enrollment fault | |
| Host trouble | Effect on annunciator | |
| Aux Supply Troub | PC4216 output overload—display may dim or fail | |
| Module E fault on PC4216 slot | Communications lost—display frozen | |
| Module LV fault | Insufficient Combus power—intermittent updates | |
| Module T tamper | Annunciator enclosure tamper |
Troubleshooting
Display Blank or Frozen
- Verify Combus wiring (4-wire) from PC4020 to annunciator driver board.
- Run PC4020 diagnostics
[04]—look for E, T, or LV on the enrolled PC4216 module driving the display. - Check AUX / Combus power—long legs may need PC4204 repower per install manual section 3.4.
- Confirm PC4216 enrollment and PGM output programming completed after wiring (manual section 4).
- Restore power only after Combus, tamper, and LED harness wiring is complete.
Wrong or Missing Icons
- Verify layout artwork matches enrolled zones and partition programming.
- Re-download or re-enter annunciator programming from LCD keypad or DLS after zone changes.
- Run Lamp Test (manual section 4.3) to verify LED matrix wiring before replacing artwork.
Intermittent Updates
- LV (low voltage) on PC4216—measure Combus at annunciator; add repower module.
- Loose Combus connections or excessive leg length—review 1,000 ft leg limits.
- SAUX+ overload elsewhere on panel dragging bus voltage down.
Tamper
- Annunciator tamper input must be wired and closed when enclosure is secure—host shows module T fault.
After PC4020 Programming Changes
Zone reassignments, partition changes, or module swaps require annunciator layout review and may need reprogramming to keep icons aligned with live zones.
Source: PC4632/PC4664 Installation Manual v1.0; PC4020 install manual.
Compatible Peripherals
Host Requirements
| Component | Requirement |
|---|---|
| Control panel | PC4010 or PC4020 MAXSYS |
| Keypad | At least one enrolled LCD4500/LCD4501 for programming |
| Bus | Combus 4-wire from PC4020 |
| Output module | PC4216 enrollment for LED driver (low-power outputs) |
| Optional | PC4204 for Combus repower on long legs |
Related MAXSYS Products
| Model | Display |
|---|---|
| PC4632 | 32 events; 8" × 11" display |
| PC4664 | 64 events; 11" × 17" display |
Only one annunciator layout per enrolled output channel—match PC4664 hardware to planned 64-event artwork.
Not Compatible
- PowerSeries or Neo panels/keypads
- PC4632/4664 on non-MAXSYS Combus implementations without PC4010/4020 host
Source: PC4632/PC4664 Installation Manual §1.1.
Installation Notes
Install the PC4664 per the PC4632/PC4664 Installation Manual after the host PC4020 is wired, powered, and has at least one enrolled LCD keypad.
Installation Sequence
- Plan layout — Decide which zones, troubles, and events appear on the 64-point display; mark supplied artwork or create custom art.
- Mount enclosure — Dry, visible location; allow access for LED matrix and driver board service.
- Assess Combus repower — If leg length or load requires it, install PC4204 per PC4204 install sheet (manual §3.4).
- Remove system power before final annunciator Combus/tamper/LED wiring (manual §3.5).
- Wire Combus, tamper, LED assembly to the PC4216 driver interface.
- Restore power — Enroll module and program PC4216 PGM outputs (manual §4, Enrollment and Wiring).
- Lamp test — Verify all LEDs before installing final artwork (§4.3).
- Install final graphic overlay — Replace draft art with finished layout.
Programming
- Program from LCD4500/LCD4501 on the PC4020 or via DLS—same as other MAXSYS modules.
- Record all annunciator programming on worksheets at back of install manual.
- Assign each displayed point to the correct zone, partition, or system event.
Wiring Notes
- Annunciator draws power via enrolled PC4216 low-power output module on Combus.
- Maintain tamper supervision on enclosure.
- Follow LED matrix pinout in manual—run lamp test before sealing enclosure.
Source: PC4632/PC4664 Installation Manual v1.0 NA (DSC official documentation).
FAQs
What does the PC4664 display?
Up to 64 events—zone openings/closings, troubles, device operation, and system status—on a graphic wall layout (11" × 17" (279 × 432 mm)).
Which panel does it work with?
PC4010 and PC4020 MAXSYS systems on Combus, programmed from an LCD keypad or DLS.
PC4632 vs PC4664?
PC4632 = 32 events, smaller display. PC4664 = 64 events, larger display for big sites. Installation and programming steps are similar.
Why is my graphic display blank?
Check PC4020 **[*, 2] troubles and diagnostics [04] for the enrolled PC4216 module—Combus E/LV** faults are the most common cause.
Can I install it before zones are wired?
The manual recommends enrolling detectors in final locations first so annunciator layout planning matches the live system.
Official manual?
DSC MAXSYS 64 Point Graphic Annunciators (ID 34) — PC4632/PC4664 Installation Manual (English NA).