DSC MAXSYS 32 Point Graphic Annunciators Error Codes

The PC4632 is a MAXSYS graphic annunciator kit that displays zone status, troubles, device operation, and system events at a glance on a wall-mounted graphic layout. The PC4632 shows up to 32 events on a 8" × 11...

Overview

The PC4632 is a MAXSYS graphic annunciator kit that displays zone status, troubles, device operation, and system events at a glance on a wall-mounted graphic layout. The PC4632 shows up to 32 events on a 8" × 11" (216 × 279 mm) display. It connects to PC4010/PC4020 MAXSYS panels over Combus and is programmed from an enrolled LCD keypad or DLS downloading software—same workflow as the rest of the MAXSYS system.

The companion PC4664 model offers 64 events on a larger display; setup and programming are similar (see shared install manual).

At a Glance

SpecificationPC4632
Display capacityUp to 32 events
Display size8" × 11" (216 × 279 mm)
Host panelPC4010 / PC4020 MAXSYS
Bus connectionCombus (4-wire)
ProgrammingLCD4500/LCD4501 keypad or DLS download
Output driverEnrolled as PC4216 low-power output module
IndicatorsZone open/close, troubles, device operation, system status
Typical useoffices, manufacturing plants, and residential applications

Before You Install One

Complete these PC4020 steps first:

  1. Plan and wire the PC4020 system (install manual).
  2. Install panel, power, and at least one LCD keypad for programming.
  3. Install and enroll zone expander modules (PC4108A, PC4116).
  4. Install and enroll detectors in final locations—makes annunciator layout planning accurate.

Then plan annunciator layout artwork (supplied templates or custom), Combus homerun, tamper, and LED matrix wiring.

Official Sources

Error Codes

The PC4632 does not maintain a separate end-user trouble code table—it reflects PC4020 system troubles and Combus module faults on its graphic display and follows host panel trouble logic.

What the Annunciator Shows

IndicationMeaning
Zone open/close iconsReal-time zone state per programmed layout
Trouble indicatorsHost panel troubles (battery, AC, FTC, zone fault, etc.)
Device operationProgrammed PGM/output or access events
Blank / frozen displayCombus comms loss, power loss, or PC4216 enrollment fault

Host Panel Troubles Affecting Display

When the graphic display stops updating, check **[*, 2]** on the host PC4020 keypad for:

Host troubleEffect on annunciator
Aux Supply TroubPC4216 output overload—display may dim or fail
Module E fault on PC4216 slotCommunications lost—display frozen
Module LV faultInsufficient Combus power—intermittent updates
Module T tamperAnnunciator enclosure tamper

Run host diagnostics [04] to identify the PC4216 module number assigned to the annunciator.

Source: PC4632/PC4664 Installation Manual; PC4020 v3.5 Installation Manual §16.

CodeMeaningSuggested Fix
IndicationMeaning
Zone open/close iconsReal-time zone state per programmed layout
Trouble indicatorsHost panel troubles (battery, AC, FTC, zone fault, etc.)
Device operationProgrammed PGM/output or access events
Blank / frozen displayCombus comms loss, power loss, or PC4216 enrollment fault
Host troubleEffect on annunciator
Aux Supply TroubPC4216 output overload—display may dim or fail
Module E fault on PC4216 slotCommunications lost—display frozen
Module LV faultInsufficient Combus power—intermittent updates
Module T tamperAnnunciator enclosure tamper