Overview
Alexor PC9155 is a wireless intrusion panel built around compact deployments and fast enrollment workflows.
Official source
- Product page: DSC Alexor PC9155 (ID 53)
- Manual basis: *Alexor Installation Guide v1.1* and *Alexor User Manual v1.1*
Capacity and I/O profile
- Wireless zones: 1 to 32
- Auxiliary output current: 200 mA
- On-board I/O points can be used either as:
- Zone 33 and Zone 34 inputs, or
- Low-current PGM outputs (50 mA)
Enrollment behavior
- Wireless enrollment section: [804]
- First keypad enrollment window is approximately 2 minutes after initial power-up
Signaling options
- Optional communicator modules include TL265, TL265GS, GS2065, and GS2060 family IP/cellular modules.
- For SIA CP-01 installations, minimum equipment is PC9155-433 control panel plus WT5500-433 keypad.
- Optional: WT5500P-433 (prox reader), PT4 prox tags, WT4989 keys, WT4901/WT4911 sirens.
Installation Notes
Suggested install sequence
- Bench power panel and enroll first keypad during the 2-minute startup window.
- Enter [804] and enroll all wireless zones.
- Decide I/O role (zones 33/34 or PGM outputs) and program accordingly.
- Validate communicator path when TL265 or GS2065 is installed.
- Complete full walk test and reporting test before final mounting.
Wireless enrollment sequence ([804])
Enroll in this order: keypad → sirens → sensors → pendants → wireless keys.
- Power panel — AC Power and Ready LEDs flash for ~2 minutes for first keypad enrollment.
- Press any button on the first WT5500 within that window.
- For additional devices, use installer
[804]— enter ESN from device sticker (6-character alphanumeric). - Assign zone 01–32 (one device per zone); accept recommended zone type or scroll options.
- Panel enters individual placement test after each sensor enrollment — verify RF before
[#]to next device. - Run global placement test after all devices are enrolled.
I/O programming ([013] options 1–2)
| Terminal | Zone mode | PGM mode |
|---|---|---|
| I/O-1 | Zone 33 input | PGM output 50 mA |
| I/O-2 | Zone 34 input | PGM output 50 mA |
Cannot use the same point as both zone and PGM simultaneously.